Compact and cable probes TM372

Brand: Endress+Hauser

Compact and cable probes TM372

Brand: Endress+Hauser

Rust Automation & Controls, Endress+Hauser's exclusive USA representative in:
 CA CO HI MT   Parts of ID ND NV   UT WY

Xpert Xpert
Heartbeat Technology Heartbeat Technology

Specs at a Glance

Max. process pressure (static):
at 20 °C: 40 bar (580 psi)
Operating temperature range:
PT 100:
-40 °C …160 °C (-40 °F …320 °F),
optional up to 190 °C (374 °F)
Response time:
t50 = 2,5 s
t90 =9,5s
Max. immersion length on request:
up to 28'' (711 mm)
others on request

Field of application

The award-winning smart temperature probe with integrated HART® transmitter and Heartbeat Technology features the world’s first RTD sensor unit capable of fully automated in-situ self-calibration. It effectively eliminates the risk of undetected non-conformities, reduces production downtime and increases product safety and process efficiency in applications of the food & beverage and life sciences industries. The device is fully compliant to FDA 21 CFR Part 11 regulations and GMP rules.

Specially designed for use in hygienic and aseptic applications in the food & beverage and life sciences industries

Measuring range: –40 to 190 °C (–40 to 374 °F)

Pressure range up to 50 bar (725 psi)

Protection class: IP65/67 or IP69

Communication: Analog output 4 to 20 mA, HART® protocol

Features

  • Risk and cost reduction thanks to self-calibration and Heartbeat Technology
  • No production downtime due to an automated and fully traceable inline self-calibration
  • Automatized documentation, memory for 350 calibration points. Printable calibration certificate - audit proof.
  • Automated 4 to 20 mA loop check for saving time and increasing safety in your process. See how iTHERM TrustSens can perform a fully automated loop check in five easy steps. The video shows the device set up and benefits for your process.
  • Elimination of non-conformities or undetected failures
  • International certifications and approvals: – EHEDG, ASME BPE, FDA, 3-A, 1935/2004, 2023/2006, 10/2011, CE CRN, CSA General Purpose, Explosion protection, e.g. ATEX/IECEx
  • Highest accuracy of measuring point through sensor-transmitter matching

Specifications

Industry

  • Chemical
  • Food & Beverage
  • Other industries
  • Life Science

Product Family

  • iTHERM TrustSens

Thermometer

Characteristic / Application

  • self-calibrating
  • imperial style
  • compact temperature probe
  • hygienic design
  • hygienic process connection

Thermowell / protection tube

  • without
  • incl. thermowell
  • incl. Tee-/elbow thermowell

Insert / probe

  • pipe version, isolated wires, not flexible

Outer diameter protection tube / Insert

  • 1/4'' (6,35 mm)
  • 3/8'' (9,53 mm)
  • 1/2" (12,7 mm)

Max. immersion length on request

  • up to 28'' (711 mm)
  • others on request

Material protection tube/ thermowell

  • 316L

Process connection

  • Weld-in adapter
  • Tri-clamp
  • Clamp-connections according to ISO2852
  • G3/4" Liquiphant
  • G1" Liquiphant
  • Varivent
  • T- and elbow thermowell

Tip shape

  • straight
  • reduced

Surface roughness Ra

  • 30 μin (0,76 μm)
  • 15 μin (0,38 μm )
  • 15 μin (0,38 μm ) electropolished

Operating temperature range

  • PT 100:
  • -40 °C …160 °C (-40 °F …320 °F),
  • optional up to 190 °C (374 °F)

Max. process pressure (static)

  • at 20 °C: 40 bar (580 psi)

Response time

  • t50 = 2,5 s
  • t90 =9,5s

Integration head transmitter

  • no (4…20mA Signal)

Ex - approvals

  • ATEX IECEx Ex ia
  • CSA C/US IS
show more