Accuracy
- ± 0.1 % of Full Scale Plus Cold Junction Errors
- ± 0.2° C (± 0.36° F) Plus 0.2 % of Reading
Ambient Temperature Range
- 0° to 50° C (32° to 122° F)
Approvals & Certifications
Circuit Protection
- Reverse Connection Protected (Power Requirement)
Input
- 2-Wire Pt100 RTD
- 3-Wire Pt100 RTD
- Thermocouple Ungrounded Typical K
Loop Resistance
- 700 ohms at 24 Vdc (Output Impedance)
Response Time
- 2 milliseconds in 70 %
- 200 milliseconds in 10 % to 90 %
Sensor / Probe Connection
Temperature Range
- 0° to 600° C (32° to 1,112° F)
Thermal Drift
- Span: 0.005 %/°C (0.0036° F)
- Zero: 0.02 %/°C (0.09° F)