XLdp Differential Pressure Transducer

Brand: Ashcroft Inc
Does not ship to OH, United States

The Ashcroft® XLdp differential pressure transducer uses patented Si-Glas technology that provides precise measurement and control at extremely low DP pressures.

This model is virtually unaffected by shock or vibration. 

An ideal choice when reliable low pressure measurement and TruAccuracy performance is needed.

Features
  • TruAccuracy performance ensures the XLdp meets its rated accuracy out of the box and is ready for installation with no additional calibration adjustments required.
  • Wide selection of differential pressure ranges down to ±0.05 in.H2O
  • Easy installation
  • Excellent overpressure protection
  • Custom pressure range calibrations are readily available
  • Superior long-term stability
  • 3-Year Warranty
  • CE Mark optional

Specifications

Brand

Accuracy

  • ± 0.25 % of Span
  • ± 0.5 % of Span

Reference Temperature

  • 70° F ±2° F (21° C ±1° C)

Stability

  • ≤ ±0.25% Span/Year at Reference Conditions

Response Time

  • 250 ms

Media

  • Clean, Dry Non-Corrosive Gases

Process Connection

  • 1/4" NPT Female
  • 1/4" Barbed Male
  • 1/8" Barbed Male

Pressure Range

  • Bidirectional: ±0.05 to ±50.00 in. H2O
  • Unidirectional: 0.10 to 50.00 in H2O

Span & Zero Effect

  • Thermal Coefficients: ± 0.015 % of Span/°F

Approvals & Certifications

  • CE
  • EMC Directive 2004/108/EC
  • IEC/EN 61326-1: Edition 1.0 Industrial, IEC/EN 61326-2-3: Edition 1.0 Annex BB Industrial
  • RoHS

Output @ 12-36 Vdc

  • 1-5 Vdc, 3-Wire
  • 1-6 Vdc, 3-Wire
  • 4-20 mA, 2-Wire

Storage Temperature

  • -40° to 82° C (-40° to 180° F)

Operating Temperature

  • -29° to 71° C (-20° to 160° F)

Compensated Temperature

  • 1.7° to 57° C (35° to 135° F)

Humidity

  • 10 to 95 % RH, Non-Condensing

Wetted Material

  • Aluminum, Titanium, PBT, Buna, Silicon, Glass, Gold, Silicone Rubber, Silicone RTV and Stainless Steel

Housing Material

  • Non-wetted: 300 Stainless Steel/Lexan

Environmental Rating

  • NEMA 2

Vibration Sweep

  • <0.05 % of Span/g Temporary Effect 0 to 60 Hz

Potentiometers

  • Externally Accessible, Non-interactive
  • Zero/Span: ± 10 % of Full Scale

Supply Current

  • < 6 mA for Voltage Output

Warm-Up Time

  • 5 seconds Max.

Mounting

  • Surface Mount

Electrical Connection

  • Screw Termination

Mounting Position Effect

  • 0.1 inH₂O: ± 0.50 % of Span/g
  • 0.25 inH₂O: ± 0.25 % of Span/g
  • 0.5 inH₂O & Higher: ± 0.10 % of Span/g

  • HVAC/R
  • Building Energy Management
  • Comfort Control Systems
  • Fume Hood Control
  • Laboratory/Clean Room
  • Hospital Room Pressurization
  • Leak Detection
  • Laminar Flow
  • Medical Lung Function
  • Breathing Equipment
  • Ultra-Low Velocity Measurement
  • Filter Monitoring
  • Fan Tracking
show more