CXLdp Differential Pressure Transmitter

Brand: Ashcroft Inc
Does not ship to OH, United States

The Ashcroft® CXLdp differential pressure transducer is designed for air handling applications including HVAC building systems, airflow metering and room pressurization control.

It utilizes Ashcroft’s SiGlas technology that enables unrivaled measurement sensitivity and long term repeatability.

The CXLdp incorporates a host of features designed to reduce installation time and costs.

It is also manufactured to Ashcroft’s straight forward TruAccuracy terminal point standard that eliminates confusion from statistically derived accuracy specifications and avoids the need for user calibration at the time of installation.

It is backed with a three year product warranty.

Features
  • TruAccuracyTM performance ensures the CXLdp meets its rated accuracy out of the box and is ready for installation with no additional calibration adjustments required
  • LED indicator for trouble-shooting, correct wiring or locating product
  • Wide selection of differential pressure ranges
  • Euro-style pluggable terminal block; reduces wiring errors and simplifies installation
  • Field-selectable output (voltage version)
  • DIN Rail Mount is standard
  • Compact design
  • Excellent overpressure protection
  • Superior long-term stability
  •  3-Year Warranty
  • CE Mark is standard

Specifications

Accuracy

  • ± 0.4 % of Span
  • ± 0.8 % of Span
  • 0.25% of Span

Stability

  • ≤±0.25% Span/year at Reference Conditions

Pressure Range

  • Bidirectional: ±0.05 to ±50.00 in. H2O
  • Unidirectional: 0.10 to 100.00 in H2O

Process Connection

  • 1/4" Barbed Male
  • 1/8 NPT Female

Media Compatibility

  • Clean, Dry and Non-corrosive Gas
  • NOT FOR USE WITH LIQUIDS

Environmental Protection

  • NEMA 1

Housing Material

  • Fire-Retardant ABS (Meets UL 94-5VA)

Reference Temperature

  • 70° F ±2° F (21° C ±1° C)

Operating Temperature

  • -17° to 71° C (0° to 160° F)

Storage Temperature

  • -40° to 82° C (-40° to 180° F)

Compensated Temperature

  • 1.6° to 54.4° C (35° to 130° F)

Humidity

  • 10 to 95 % RH, Non-Condensing

Response Time

  • 250 ms Standard

Visual Indication

  • LED Visual Indicator

Electrical Connection

  • 12-26 Gauge Wire
  • Euro Style Pluggable Terminal Block Accepts

Mounting

  • Threaded Fastener & 35 mm DIN Rail Mount

Output

  • 0-10 Vdc
  • 0-5 Vdc
  • 4-20 mA

Approvals & Certifications

  • CE/UKCA
  • EMC Directive 2004/108/EC
  • IEC/EN 61326-1: Edition 1.0 Industrial, IEC/EN 61326-2-3: Edition 1.0 Annex BB Industrial
  • RoHS

Supply Voltage & Current

  • 11.5-36 Vdc or 24 Vac (±20%), 4.5 mA
  • 12-36 Vdc, 21.5 mA
  • 14-36 Vdc or 24 Vac (±20%), 6 mA

Thermal Coefficients

  • Zero: ±0.03% of span/°F
  • Span: ±0.03% of span/°F

  • HVAC/R
  • Critical Environments
  • Building / Comfort Control Systems
  • Fan Monitoring
  • Duct Flow
  • Fume Hood Control
  • Clean Room
  • Filter Monitoring