Pressure Transmitter - R-1

Brand: WIKA Alexander Wiegand SE & Co. KG

The model R-1 pressure transmitter has been optimally designed for the specific requirements of refrigeration and air-conditioning applications. Its monolithic construction dispenses with the need to use seals on the process side. This enables the model R-1 to be used with all typical refrigerants (e.g. freon and ammonia).
Features
  • Wetted parts from stainless steel. 
  • Resistant to all common refrigerants. 
  • Special case design for the best possible condensation tightness. 
  • Private labelling possible. 

Specifications

Power Supply

  • The Power Supply depends on the selected output signal
  • DC 0.5 ... 4.5 V: DC 4.5 ... 5.5 V
  • DC 0 ... 10 V: DC 14 ... 30 V
  • DC 1 ... 5 V: DC 8 ...30 V
  • 4 ... 20 mA: DC 7 ...30 V

Temperature

  • 59° to 77° F (15° to 25° C)

Atmospheric Pressure

  • 12.5 ... 15.4 psi (860 ... 1,060 mbar)

Humidity

  • 45 ... 75 % Relative

Nominal Position

  • Calibrated in vertical Mounting position with process Connection facing downwards.

Accuracy at Reference Conditions

  • Including Non-linearity, hysteresis, zero offset and end value deviation (Corresponds to measured error per IEC 61298-2).
  • ≤ 2 % of Span

Temperature Error at -13 ... 185° F (-25 ... +85° C)

  • Mean Temperature coefficient of Span: ≤ 0.3 % of Span/10 K
  • Mean Temperature coefficient of zero point: typical ≤ 0.5 % of Span/10 K

Long-term Drift (per IEC 61298-2)

  • ≤ 0.3 % of Span/Year

Settling Time

  • ≤ 5 milliseconds

Ingress Protection (per IEC 60529)

  • The Stated ingress Protection only applies when plugged in using mating Connectors that have the appropriate ingress Protection.
  • Cable outlet: IP69K
  • Metri-Pack Series 150: IP67
  • Circular Connector M12 x 1: IP67
  • The ingress Protection depends on the Type of Electrical Connection

Temperatures

  • Ambient: -25° to +85° C -13° to +185° F
  • Medium: -40° to +100° C -40° to +212° F
  • Storage: -25° to +85° C -13° to +185° F

Stability

  • The Pressure transmitter is resistant to the industrial Standard refrigerants

  • Compressor staging
  • Condenser fan controls
  • Chiller systems

Documentation

show more