8111 Vibrating Level Switch
Brand: Burkert Fluid Control SystemsThe 8111 is a vibrating level switch for liquids, using a tuning fork for level detection. It is designed for industrial use in areas of process technology and can be used in liquids. Typical applications are overfill or dry run protection.
Depending on the version it is also used for monitoring or control of levels in hazardous environments, even for combustible liquids, gases, fogs or vapours.
Due to the simple and rugged measuring system, the 8111 is virtually unaffected by the chemical and physical features of the liquid. It works even under unfavourable conditions such as turbulence, air bubbles, foam generation, buildup or varying products.
Features
- For universal use as overfill or dry run protection system
- Setup without adjustment
- For food and beverage industry thanks to surface finishing < 0.8 µm
- ATEX approvals
Specifications
Environmental Protection
- IP66
- IP67
Cover Material
- Polycarbonate (PC)
Seal Material
- EPDM
Housing Material
- Plastic PBT (Polyester)
- Stainless Steel 316L (1.4404)
- PPS
Process Connection
- Thread G or NPT, 3/4" or 1"; Clamp 2"
Process Pressure
- psi: -14.51 to 928.64 (kPa: -100 to 6,400, bar: -1 to 64)
Process Temperature
- -50° to 150° C (-58° to 302° F)
Electrical Connection
- 1 or 2 Cable Glands M20 x 1.5
Repeatability
- 0.1 mm
Hysteresis
- Approximately 2 mm (0.08") with Vertical Installation
Dynamic Viscosity
- 0.1 to 10,000 mPa-s (with Density 1)
Switch Type
- 2 Floating SPDTs
- Relay (DPDT)
Density Range
- 0.5 to 2.5 g/cm³ (DIP Switch)
- 0.7 to 2.5 g/cm³
Ambient Temperature
- Operating: -40° to 70° C (-40° to 158° F)
- Storage & Transport: -40° to 80° C (-40° to 176° F)
Approvals & Certifications
- ATEX: EN 50014, EN 50020, EN 50284
- CE
Operating Voltage
- 20-253 Vac, 50/60 Hz
- 20-72 Vdc
Power Consumption
- 1-8 VA (AC)
- Approx. 1.5 W (DC)
- Food and Beverage Industry
- Chemical Industry - Solvents, Reactors
- Water/Sewage Water Plants
Documentation
Product Manuals
- Operating Instructions Type 8111 | Level switch with contactless electronic switch pdf 1.4 MB
- Operating Instructions Type 8111 | Level switch with NAMUR output pdf 1.3 MB
- Operating Instructions Type 8111 | Level switch with relay output pdf 1.4 MB
- Operating Instructions Type 8111 | Level switch with relay output pdf 1.3 MB