3500 Series Dual Loop Controller/Programmer

Brand: Eurotherm
Does not ship to Ohio, United States

The emphasis is on flexibility yet the 3500 controllers still maintain ease of use. 

A simple 'Quick Start' process is used to configure all the basic functions essential to controlling your process. 

This includes input sensor type, measurement range, control options and alarms making 'Out the Box' operation truly achievable.

More advanced features are configured using a PC based graphical configuration tool enabling users to pick function blocks from a library then connect them together using soft wiring.
Features
  • 2 PID loops
  • 50 Programs
  • Precision PV input
  • Carbon potential
  • Maths/logic/timers
  • Custom user interface
  • Recipes
  • Digital communications
    • Modbus RTU Master and
    • Slave
    • Ethernet Modbus TCP
    • Profibus DP network
    • DeviceNet network
  • OEM Security
  • Multi-language support (English, French, German, Spanish and Italian)

Specifications

Brand

Accuracy

  • Analog Control Output: < ± 2.5 %
  • Analog Input Module (Calibration Accuracy): ± 0.2 % of Reading ± 1 LSD
  • Analog Re-transmission Output: < ± 0.5 %
  • Dual 4-20 mA OP / 24 Vdc TxPSU: < ± 1 %
  • Main Process Variable Input (Calibration Accuracy): < ± 0.1 % of Reading ± 1 LSD
  • Thermocouple (Cold Junction Accuracy): < ± 1° C (1.8° F) at 25° C (77° F) Ambient
  • Thermocouple (Linearisation Accuracy): < 0.2 % of Reading
  • Thermocouple of Linearisation Accuracy: < 0.2 % of Reading

Approvals & Certifications

  • FC (Factory Calibration Certificate)

Approvals & Certifications

  • CE
  • cUL Listed (File E57766)
  • EMC: Emissions & Immunity BS EN 61326
  • GOST

Communication

  • 2, 4-Wire EIA-485 Modbus Master, EI-Bisynch
  • 2-Wire EIA-85 EI-Bisynch
  • DeviceNet
  • EIA-232 Modbus
  • Ethernet Modbus 10 Base TCP/IP
  • Modbus RTU Slave
  • Modbus/TCP
  • PROFIBUS DP
  • RJ45
  • RS-232 EI-Bisynch, Modbus Master

Current

  • 100 mV Range (Input Leakage Current): < 1 NA
  • 2 V Range (Input Leakage Current): < 10 NA
  • 40 mV, 80 mV, 2 V Range (Input Leakage Current): ± 14 NA
  • Inrush Current [High Voltage (VH)]: 30 A Duration < 100 μS
  • Inrush Current [Low Voltage (VL)]: 15 A Duration < 100 μS
  • Resistance Thermometer (Bulb Current): 200 μA
  • Resistance Thermometer (Bulb Current): 300 μA

Display

  • Operator Interface (Main PV Display): 4-1/2-Digits Green - 3508
  • Operator Interface (Main PV Display): 5-Digits, Green - 3504
  • Operator Interface (Message Display): 16-Character Header & 3 Lines of 20 Characters - 3504
  • Operator Interface (Message Display): 8-Character Header & 3 Lines of 10 Characters - 3508
  • Operator Interface: STN LCD with Backlight

Electrical Connectors

  • I/O Expander (20 I/O, 40 I/O): 4 Form C Relays
  • I/O Expander (20 I/O, 40 I/O): 6, 16 Form A Relays

Electrical Contacts

  • Normally Closed
  • Normally Open

Electrical Rating

  • AA Relay: Min. 1 mA at 1 Vdc
  • Relay Modules, I/O Expander (Relay): Max.
  • Relay Modules, I/O Expander (Relay): Min. 100 mA at 12 Vdc
  • Transmitter PSU Module: 24 Vdc at 20 mA
  • Triac Modules: < 0.75 A at 264 Vac Resistive

Environmental Protection

  • IP52
  • IP65
  • NEMA 12

Excitation Voltage

  • Potentiometer Input: 0.5 Vdc Supplied by Module

Function

  • Logic Input & Output, Relay & Triac Modules: Alarm Acknowledge
  • Logic Input Modules: Key Lock Function
  • Logic Input Modules: Manual
  • Logic Input Modules: Program Control
  • Logic Output, Relay & Triac Modules, Dual 4-20 mA OP / 24 Vdc TxPSU: Control Output
  • Logic Output, Relay & Triac Modules: Event
  • Potentiometer Input: Remote Set Point
  • Potentiometer Input: Valve Position
  • Triac Modules: Status

Humidity

  • Operation, Storage: 5 to 95 % Relative Humidity, Non-Condensing

Input

  • 10 V Range: -3 to 10 V
  • 2 V Range: -1.4 to 2 V
  • 40 mV Range: -40 to 40 mV
  • 80 mV Range: -80 to 80 mV
  • Analog (2 V Range): -0.2 to 2 V
  • Digital: Closed 0-7.3 Vdc
  • Digital: Open 10.8-24 Vdc
  • Logic Input Modules, I/O Expander of Logic Input, Voltage Level: 10.8-30 Vdc at 2.5 mA (Normally Closed)
  • Logic Input Modules, I/O Expander of Logic Input, Voltage Level: -3 to 5 Vdc at < -0.4 mA (Normally Open)
  • Thermocouple, 100 mV Range: -100 to 100 mV
  • Thermocouple: 40-80 mV

Input Impedance

  • 10 V Range: > 69 kiloohms
  • 10 V Range: 62.5 to 667 kiloohms
  • 2 V, 100 mV Range: > 100 megaohms
  • Resistance Thermometer, 40 mV, 80 mV, 2 V Range: 100 megaohms

Isolation

  • 264 Vac Double Insulation between Channels

Linearity

  • 10 V Range (Linearity Error): < 0.007 % of Reading for Zero Source Resistance
  • 2 V Range: < 0.015 % (Best Fit Straight Line)
  • Resistance Thermometer (Linearity Error): < ± 0.03 % (Best Fit Straight Line)
  • Resistance Thermometer, 40 mV, 80 mV, 100 mV, 2 V Range, 10 V Range (Linearity Error): < 0.033 % (Best Fit Straight Line)

Mounting

  • 1/4” DIN Mounting - 3504
  • 1/8” DIN Mounting - 3508
  • Panel Mount

Operating Temperature

  • 0° to 50° C (32° to 122° F)

Output

  • Analog (Rating): 0-10 Vdc > 500 ohms
  • Analog (Rating): 0-20 mA < 600 ohms
  • Dual 4-20 mA OP / 24 Vdc TxPSU: 24 Vdc, 22 mA
  • Dual 4-20 mA OP / 24 Vdc TxPSU: 4-20 mA DC, < 1 kiloohms

Power Requirement

  • 100-230 Vac, ± 15 %
  • 24 Vac +10 % - 15 %
  • 24 Vdc, 20 % -15 % ± 5 % Ripple Voltage
  • 48 to 62 Hz, 20 W, Max.

Resistance

  • Input: Closed 1,200 ohms
  • Logic Input Modules (Contact Closure): Closed 28 kiloohms
  • Potentiometer Input: 100 ohms to 15 kiloohms
  • Resistance Thermometer (Lead Resistance): 0 to 22 ohms
  • Resistance Thermometer: 0 to 400 ohms [-200° to 850° C (-328° to 1,562° F)]
  • Transducer PSU Module (Bridge Resistance): 300 ohms to 15 kiloohms
  • Transducer PSU Module (Internal Shunt Resistor): 30.1 ohms at 0.25 %, used for Calibration of 350 ohms Bridge at 80 %

Resolution

  • 10 V Range (Effective Resolution): 15.4-bits
  • 10 V Range: < 200 μV with 1.6 seconds Filter
  • 10 V Range: < 550 μV with 1.6 seconds Filter
  • 2 V Range (Effective Resolution): 16.2-bits
  • 2 V Range: < 90 μV with 1.6 seconds Filter
  • 2 V Range: 30 μV with 1.6 seconds Filter Time
  • 40 mV Range: < 1 μV with 1.6 seconds Filter
  • Analog Control Output: 10-bits
  • Analog Re-transmission Output, Dual 4-20 mA OP / 24 Vdc TxPSU: 11-bits
  • Resistance Thermometer (Effective Resolution): 13.7-bits
  • Resistance Thermometer: < ± 0.08° C (0.144° F) with 1.6 seconds Filter
  • Resistance Thermometer: < 0.050° C (32.09° F) with 1.6 seconds Filter
  • Thermocouple, 100 mV Range (Effective Resolution): 15.9-bits
  • Thermocouple, 80 mV, 100 mV Range: < 3.3 μV with 1.6 seconds Filter Time
  • Thermocouple, Resistance Thermometer, 40 mV, 80 mV, 2 V, 10 V Range: 16-bits

RTD Type

  • Pt20

Sample Rate

  • Analog Input Module, Main Process Variable Input: 9 Hz (110 milliseconds)

Sensor, Probe Type

  • B Thermocouple
  • C Thermocouple
  • J Thermocouple
  • K Thermocouple
  • L Thermocouple
  • N Thermocouple
  • PL2 Thermocouple
  • R Thermocouple
  • S Thermocouple
  • T Thermocouple

Storage Temperature

  • -10° to 70° C (14° to 158° F)

Supply Voltage

  • 24 Vac/dc
  • 85-264 Vac
  • Interrupt Protection (Low Voltage): Holdup > 10 milliseconds at 20.4 Vrms
  • Interrupt Protection: Holdup > 10 milliseconds at 85 Vrms

Update Time

  • Loop Update: 110 milliseconds

Vibration

  • 2 G Peak, 10 to 150 Hz

Voltage

  • Transducer PSU Module (Bridge Voltage): Software Selectable 10 Vdc
  • Transducer PSU Module (Bridge Voltage): Software Selectable 5 Vdc

show more