Accuracy
- ± [0.30 + 0.005*ltl]° C
- ± 0.5 % of Full Scale
- Class B Per EN 60751 (IEC 751)
Ambient Temperature Range
- -40° to 85° C (-40° to 185° F)
Applications
- HVac Systems
- Industrial Machinery & Machine Tools
- Refrigeration Systems
- Storage Tanks
- Water Systems
Approvals & Certifications
- CE Compliant to Suppress RFI, EMI, & ESD
Electrical Connectors
- 36” Cable
- Hirschmann Connection with ISO 4400 1/2″ NPT Conduit
- M12 x 1, 4-Pin
- Hirschmann (DIN EN 175301-803 Form A)
Electrical Protection
- Overvoltage
- Reverse Polarity
- Short Circuit
Environmental Protection
- P65 According to EN 60529 / IEC 529
Load Limit
- ≤ (VPower-10) / 0.020 Amp for 4-20 mA Output
- ≤ 10,000 ohms for 0-10 Vdc Output
- ≤ 4,500 ohms for 0.5-4.5 Vdc Output
- ≤ 5,000 ohms for 1-5 Vdc Output
NPT Connection
- 1/2” NPT Male
- 1/4” NPT Male
Output
- 0-10 Vdc, 3-Wire
- 0-5 Vdc, 3-Wire
- 1-5 Vdc, 3-Wire
- 4-20 mA, 2-Wire
Power Requirement
- 10-30 Vdc (4-20 mA, 2-Wire) / (0-5 Vdc, 3-Wire) / (1-5 Vdc, 3-Wire)
- 14-30 Vdc (0-10 Vdc, 3-Wire)
Sensor Protection
- Burn-Out Protected from 3.3-23 mA
Stem Length
- 12” (30.5 cm)
- 2.5” (6.35 cm)
- 4” (10.2 cm)
- 6” (15.2 cm)
- 9” (22.9 cm)
Storage Temperature
- -40° to 85° C (-40° to 185° F)
Temperature Range
- Standard Ranges from -40° to 538° C (-40° to 1,000° F)