Process transmitter Limit Switch / Transmitter RMA42
Brand: Endress+HauserProcess transmitter Limit Switch / Transmitter RMA42
Brand: Endress+Hauser
Lean Specs at a Glance
Output:
2 x Analog (current, voltage)
Display:
LCD
7 segment
Multicolour
Bargraph
TAG unit
Colour change in case of failure
7 segment
Multicolour
Bargraph
TAG unit
Colour change in case of failure
Power Supply:
Wide range power supply 24 to 230 V AC/DC (-20 % / +10 %) 50/60 Hz
Input:
2 x universal (current, voltage, R, RTD, TC, resistance)
Field of application
The process transmitter RMA42 displays analog measured values and is controlled by a microcontroller. With the integrated loop power supply, two-wire sensors can be powered. The universal inputs enable the connection of current, voltage, RTDs and TCs. The multicolor LCD display with 7-segment bar graph allows the unit to be displayed.
Features
- One device to cover a multitude of functions and applications: loop power supply, barrier, integrated relays, calculations and indication of measured values.
- Perfect supplement for level measurements as it can be used as overfill protection, offers calculations like average or difference, e.g. for differential pressure applications and can be used to linearize a tank.
- Easy on site configuration with 3 buttons and remote commissioning from a safe and convenient location.
Specifications
Brand
Field of Application
- Industrial gases
- Convenience food
- Cement, lime and gypsum
- Biogas, biomass
- Dairy and dairy products
Industry
- Chemical
- Water, Wastewater & Waste
- Food & Beverage
- Power & Energy
- Mining, Minerals & Metals
- Oil & Gas
- Other industries
- Life Science
Target Customer
- Food & beverage industry
- Marine business
- Refineries
- Oil & Gas industry
- Petrochemical industry
Process transmitter
Measuring principle
- Process transmitter
Function
- Universal process and temperature transmitter with control unit
Loop power supply
- 24 V intrinsically safe loop power supply
Power Supply
- Wide range power supply 24 to 230 V AC/DC (-20 % / +10 %) 50/60 Hz
Input
- 2 x universal (current, voltage, R, RTD, TC, resistance)
Output
- 2 x Analog (current, voltage)
Software functions
- Internal software for calculations, linearization, limit monitoring
- Monitoring of sensor wires according NAMUR NE43
- Application package differential pressure measurement
Certificates
- ATEX
- FM
- NEPSI
- CSA
- UKCA
- UR C/US
- marine approval
- KTA
- German WHG overfill protection
SIL
- 2
Display
- LCD
- 7 segment
- Multicolour
- Bargraph
- TAG unit
- Colour change in case of failure
Interface
- Not defined
Dimensions (WxHxD)
- 45 x 115 x 118 mm (1.77" x 4.53" x 4.65")