P200 Pneumatic To Current P/I Transducer

Brand: ControlAir

ControlAir’s P200 and P290 P/I transducers represent outstanding value in pneumatic to current technology.

All solid state circuitry converts standard 3-15, 3-27 or 6-30 psig instrument air into 4-20 or 10-50 mA outputs (4-20 mA only for FM and CSA approval) with uncompromising accuracy and durability. Custom pressure ranges are also available. 

The P200’s explosion - proof housing allows it to stand up to the most hazardous and demanding applications. 

The P200 is FM approved and CSA certified as NEMA 4 (Enc. 4) for all locations and explosion-proof for Class I, Div. 1, Groups A, B, C, D; dust ignition-proof for Class II, Div. 1, Groups E, F, G; and suitable for Class III, Div. 1 locations. 

The P290 is available with high density DIN rail adapters, offering space saving flexibility with easy plug-in installation.
Features
  • ±0.10% Accuracy
  • Non-interactive Calibration
  • Transient, Over-current and Reverse Polarity Protection 
  • RFI Immune

Specifications

Input

  • 3 - 15 psig (0.2 - 1 bar)
  • 6 - 30 psig (0.4 - 2 bar)
  • 3 - 27 psig (0.2 - 1.8 bar)

Input Maximum

  • 3 Times Full Scale without Calibration, 4 Times Full Scale without Failure

Output (2 Wire)

  • 10-50 mA
  • 4-20 mA

Allowable Loads

  • 700 Ω

Accuracy

  • ± 0.15 % of Span Guaranteed, ± 0.10 % of Span Typical.

Repeatability

  • ± 0.10 % of Span Max., ± 0.03 % of Span Typical

Resolution

  • Infinite

Response Time to 99% of Step Change

  • 10 m/sec

Power Supply

  • 10 Vdc min. to 42 Vdc Max. at Input Terminals. Can Indefinitely Withstand Up to 100 Vdc without Failure

RFI/EMI Effect

  • Meets or Exceeds SAMA PMC 33.1, 1978, 2-abc: 0.1 % of Span at 10 Volts/Meter

Ambient Temperature Limits

  • -40° to 161° F (-40° to 72° C)

Temperature Range (Storage)

  • -60° to 161° F (-51° to 72° C)

Connections - Signal Air

  • 1/4” NPT Female

Connections - Electrical Wiring

  • 1/2” NPT Female to Barrier Terminal Strip
show more