Intrinsically Safe Repeater Power Supply - IS Barrier
Brand: WIKA Alexander Wiegand SE & Co. KGThe model IS barrier intrinsically safe barrier has been designed for applications in combination with intrinsically safe 4 ... 20 mA sensors.
By using different connection terminals, 2-wire as well as 4-wire transmitters can be connected.
Features- Input 0/4 ... 20 mA, supplying and non-supplying
- Suitable for SIL 2 per IEC 61508/IEC 61511
- Bidirectional HART® signal transmission
Specifications
Input
- Active Current Input, intrinsically safe
Input Signal, Current
- 4 ... 20 mA
Current Limitation
- 25 mA
Transmitter Power Supply
- > DC 16 V (For 20 mA)
- > DC 15.3 V (For 22.5 mA)
Under & Overload Signal Range
- 0 to 24 mA (Extended transmission Range for diagnostics)
Output
- Current output (Active and passive)
- Transfer 1: 1 to Input signal
Load
- < 1,000 Ω at 20 mA
- < 825 Ω at 24 mA
Output Ripple
- < 20 mVef
Behaviour in the Event of An Error in Accordance with NE43
- 0 mA (Cable break in Input)
- ≥ 22.5 mA (Cable short Circuit in Input)
Input / Output / Voltage Supply
- Insulation Voltage: 300 Veff
- Overvoltage Category II
- Pollution Degree 2
- Safe isolation in accordance with EN 61010-1: 50 Hz, 1 min.
- Test Voltage: 2.5 kV
Input / Output
- Voltage peak value in accordance with EN 60079-11: 375 V
Input / Voltage Supply
- Voltage peak value in accordance with EN 60079-11: 375 V
Power Supply
- Voltage Range: DC 19.2 ... 30 V
- Nominal Voltage: DC 24 V
Maximum Current Supply
- < 55 mA (DC 24 V / 20 mA / 250 Ω)
- < 76 mA (DC 24 V / 20 mA / 1,000 Ω)
Dissipation Loss
- Output, active: < 1.1 W (DC 24 V / 20 mA / 1,000 Ω), < 0.95 W (DC 24 V / 20 mA / 250 Ω)
- Output, active: < 1.1 W (DC 24 V / 20 mA / 1,000 Ω) < 0.95 W (DC 24 V / 20 mA / 250 Ω)
Power Consumption (Output Active)
- Power consumption (Output active)
- < 1.3 W (20 mA / 250 Ω)
Transmission Error
- < 0.05 % of end value (Typical)
- < 0.10 % of end value (Max.)
Temperature Coefficient
- < 0.004 %/K, Typical
- < 0.01 %/K (Max.)
Step Response (10 ... 90 %)
- < 200 μs (With step 4 mA ... 20 mA, load 600 Ω)
- < 600 μs (With step 0 mA ... 20 mA, load 600 Ω)
Ingress Protection
- IP20
Overvoltage Category
- II
Flammability Class in Accordance with UL 94
- V0
Pollution Degree
- 2
Permissible Ambient Temperatures
- Operation: -20° to +60° C
- Storage: -40° to +80° C
Permissible Humidity
- 10 ... 95 % (No Condensation)
Mounting Position
- as Required
- Chemical, petrochemical industry
- Oil, natural gas
- Machine building