Fluke 1630-2 FC Earth Ground Clamp
Brand: Fluke CorporationThe 1630-2 FC clamp measures earth ground loop resistances for multi-grounded systems using the dual-clamp jaw.
This test technique eliminates the dangerous and time-consuming activity of disconnecting parallel grounds, as well as the process of finding suitable locations for auxiliary test stakes.
You can also perform ground tests in places that were previously difficult: inside buildings, on power pylons or anywhere you don't have access to soil to place auxiliary test stakes.
Features- Test the grounding components of equipment in hard-to-reach spaces, including areas that are indoors or fully paved and do not permit driving auxiliary test stakes.
- AC Leakage Current Measurement: Identify AC leakage without disconnecting your earth ground stake from the grounding system
- Rugged: Heavy-duty clamp jaw stays in alignment and calibration on tough jobsites
- Logging measurement: Saves up to 32,760 measurements in memory
Specifications
Brand
Maximum Voltage to Earth Ground
- 1000 V
Frequency Range
- 40 Hz to 1 kHz
Ingress Protection
- IEC/EN 60529: IP30 with jaw closed
Operating Temperature
- -10° C to + 50° C
Reference Temperature
- 23° C ± 5° C
Temperature Coefficient
- 0.15 % x (specified accuracy)/ °C
Input (Ω) Range
- 0.474: 0.417 to 0.531
- 0.5: 0.443 to 0.558
- 10: 9.55 to 10.45
- 100: 96 to 104
Safety
- General: IEC/EN 61010-1: Pollution Degree 2 IEC/EN 61557-1
- Measurement: IEC/EN 61010-2-032: CAT IV 600 V / CAT III 1000 V
- Current clamp for leakage current measurements: IEC/EN 61557-13: Class 2, ≤ 30 A/m
Output Power
- < 10 mW
Documentation
Data Sheets
Product Literature
- 1630-2/1630-2 FC Calibration Manual pdf
- 1630-2/1630-2 FC Quick Reference Guide pdf
- 1630-2/1630-2 FC Quick Reference Guide Supplement pdf
- 1630-2/1630-2 FC Safety sheet pdf
- 1630-2/1630-2 FC Safety Sheet Supplement pdf
- 1630-2/1630-2 FC Statement of Memory Volatility pdf
- Radio Frequency Data Class B Instruction Sheet pdf