FieldSense AC Voltage True-rms
- Range: 600 V
- Resolution: 1 V
- Accuracy: ± (3 % + 3 counts)
FieldSense AC Current True-rms
- Range: 200.0 A
- Resolution: 0.1 A
- Accuracy: ± (3 % + 3 counts)
FieldSense Frequency
- Resolution: 1 Hz
- Accuracy: ± (1 % + 2 counts)
Volts ac True-rms
- Range: 600 V
- Resolution: 1 V
- Accuracy: ± (1.5 % + 2 counts)
Volts dc
- Range: 600 V
- Resolution: 1 V
- Accuracy: ± (1 % + 2 counts)
Resistance
- Range: 2000 Ω
- Resolution: 1 Ω
- Accuracy: ± (1 % + 2 counts)
Operating Temperature
- -10° C to +50° C
- 14° F to 122° F
Relative Humidity
- 0 % to 90 %, 5° C to 30° C (41° F to 86° F)
- 0 % to 75 %, 30° C to 40° C (86° F to 104° F)
- 0 % to 45 %, 40° C to 50° C (104° F to 122° F)
Safety
- IEC/EN 61010-1: Pollution Degree 2
Electromagnetic Environment