Fluke 1770 Series Three-Phase Power Quality Analyzers

Brand: Fluke Corporation

When you invest in Fluke 1770 Series Three-Phase Power Quality Analyzers, you want your money to go as far as possible. 

Fluke Premium Care is a paid offering that provides coverage above and beyond the 1770 Series original product warranty, so you don’t need to worry about unexpected downtime caused by damaged test equipment, accessories, or tools in need of calibration or repair.

Fluke 1770 Series Three-Phase Power Quality Analyzers eliminate the complexities of power quality logging, troubleshooting, and analysis. 

Engineered to be the faster, easier way to perform power quality studies, the 1770 Series offers automatic measurements, a straightforward user interface and setup, best-in-class specifications, and a simplified reporting platform. 

The instrument can also be powered directly from the measurement circuit, eliminating the need to find a power outlet or use a lengthy extension cord

With the 1770 Series you’ll never miss a critical power quality event—from fast transients up to 8 kV, harmonics up to 30 kHz, dips and swells, as well as the voltage, current, and power measurements that enable you to characterize your electrical system.
Features
  • Automatically measure power and power quality parameters
  • At-a-glance power quality health for faster troubleshooting
  • Easily view V/A/Hz, power, dips, swells, and harmonics data
  • Capture high-speed transients up to 8 kV
  • Power directly from measurement circuit without a line cord

Specifications

Number of Voltage Inputs

  • 4 inputs, 3-Phases and neutral referenced to PE (5 connectors)

Measurement Category

  • 1000 V CAT III / 600 V CAT IV

Maximum Input Voltage

  • 1000 V RMS / 1000 V dc

Input Impedance

  • 10 MΩ between P-P and P-N
  • 5 MΩ between P-PE and N-PE

Voltage Bandwidth

  • DC to 30 kHz for PQ measurements, excluding transients

Measurement Range

  • ± 8 kV

Sampling Rate

  • 1775: 1 MS/s
  • 1777: 1 MS/s, 20 MS/s

Bandwidth

  • DC to 1 MHz

Voltage Resolution

  • 14-bit synchronous sampling

Number of Current Inputs

  • 4 inputs 3-Phases and Neutral, range selected automatically to attached sensor

Current Bandwidth

  • DC to 30 kHz

Current Resolution

  • 24-bit synchronous sampling

Input Impedance

  • 11 kΩ

Standard Compliance

  • Power: IEEE 1459
  • Harmonics: IEC 61000-4-7: Class 1 & IEEE 519 (short time and very short time harmonics)
  • Flicker: IEC 61000-4-15 Class F1
  • Power quality: IEC 61000-4-30 Class A, IEC 62586 PQI-A-PI
  • Power quality compliance: EN 50160 + GOST + NEQUAL + NETCODE + FOL

Operating Temperature

  • -10° C to 50° C

IP Rating

  • IEC 60529: IP50

Vibration

  • IEC 60721-3-3 / 3M2

Voltage Range

  • 100 V - 600 V -15 % / +10 %
show more