Type S056 Magnetic Inductive Sensor with Hygienic Process Connection
Brand: Burkert Fluid Control SystemsThe type S056 magnetic inductive flow sensor (compact or separated version) is recommended for applications with low flow rate and liquids with a minimal conductivity.
When combined with the SE58 M or SE58 L transmitters (minimum required conductivity: 5 µS/cm) it builds a flow measurement device with different performance, functions, materials and approvals with an appropriate suitability for the respective application depending on the individual requirements.
With the SE58 M and SE58 L compact devices or remote versions are created for which the transmitter and sensor are connected by 2 cables up to a maximum length. Standard process connections available for the S056 are clamp or thread (dairy thread) connections.
When connected to an actuator such as a valve, the S056 sensor in combination with the SE58 L transmitter can also be used to control high-precision filling operations.
Features
- For connection to a type SE58 transmitter (with display, in compact or remote version) for flow measurement
- Hygienic variant, 3A certification variant, 3A certification
- For food, beverage or pharmaceutical applications
- Flow measurement 0.2... approx. 4,500 l/min for DN 03... DN 100
Specifications
Wetted Material
- Electrode & Clamp: Stainless Steel 316L
- Lining: PTFE (conform to FDA)
- Seal: FKM (conform to FDA), EPDM (on request, conform to FDA)
Sensor Housing Material
- Stainless Steel 304/1.4301
Junction Box
- Only for Remote Sensor: Stainless Steel 304 (1.4301) Polished
Pipe Diameter
- DN 03 to DN 100
Measuring Range
- 0-10 l/h to 0-280 m3/h
Measurement Deviation
- In Compact or Remote L Variant: ≤ ± 0.2 % of the Measured Value for Flow Velocity > 0.5 m/s
- In Compact or Remote M Variant: ≤ ± 0.8 % of the Measured Value for Flow Velocity > 0.5 m/s
- In Compact S Variant: ≤ ± 0.5 % of the Measured Value for Flow Velocity > 0.5 m/s
Repeatability
- In Compact or Remote L Variant: ≤ ± 0.1 % of the Measured Value for Flow Velocity > 0.5 m/s
- In Compact or Remote M Variant: ≤ ± 0.4 % of the Measured Value for Flow Velocity > 0.5 m/s
- In Compact S Variant: ≤ ± 0.25 % of the Measured Value for Flow Velocity > 0.5 m/s
Velocity Range
- 0.4 to 10 m/s
Certification & Approval
- CE
- 3A
- FDA
- EC 1935/2004 declaration
Fluid Temperature
- -20° to 130° C (-4° to 2660° F)
Ambient Temperature
- -20° to 60° C (-4° to 140° F)
Pipe Connection
- DIN 11851, clamp ISO 2852 or clamp BS 4825 (SMS 1146 (from DN 10) on request)
Electrical Connection
- 2 Cable Glands PG9 (for remote variant of the sensor)
Relative Air Humidity
- ≤ 90 %, Without Condensation