Capacitance level switch Liquipoint FTW31
Brand: Endress+HauserCapacitance level switch Liquipoint FTW31
Brand: Endress+Hauser
Fundamental Specs at a Glance
Process temperature:
-40 °C ... 100 °C
(-40 °F ... 212 °F)
(-40 °F ... 212 °F)
Min. conductivity of medium:
10 µS/cm
Process pressure / max. overpressure limit:
Vacuum ... 10 bar
(Vacuum ... 145 psi)
(Vacuum ... 145 psi)
Field of application
The Liquipoint FTW31 is a rod probe for point level detection in conductive liquids. With up to 5 rods, it offers numerous measuring possibilities such as overfill prevention, dry running protection, two-point control of pumps or multiple point detection. The device does not require calibration.
Features
- Detect up to five point levels with one probe
- Two-point control and additional MAX and MIN detection
Specifications
Brand
Industry
- Chemical
- Water, Wastewater & Waste
- Food & Beverage
Product Family
- Liquipoint
Point Level / Liquids
Characteristic / Application
- Compact rod probe with multipoint detection, possible up to 5 switch points. Simple rod shortening.
Supply / Communication
- DC PNP 10,8V ... 45V
- Relay 20V ... 230V AC
- Relay 20V ... 55V DC
Ambient temperature
- -40 °C ... 70 °C
- (-40 °F ... 158 °F)
Process temperature
- -40 °C ... 100 °C
- (-40 °F ... 212 °F)
Process pressure / max. overpressure limit
- Vacuum ... 10 bar
- (Vacuum ... 145 psi)
Min. conductivity of medium
- 10 µS/cm
Main wetted parts
- 316L, PP, PPS
Max. tensile strength
- 1000 N
Process connection
- G 1 1/2
- NPT1 1/2"
Sensor length
- 0.1m ... 4m
- (3.9" ... 157")
Communication
- DC PNP
- Relay
Certificates / Approvals
- ATEX, EAC Ex
Safety approvals
- Leakage Detection
Components
- Transmitter: FTW325
Application limits
- Observe min. medium conductivity