3275 2/2-Way Motor Valve

Brand: Burkert Fluid Control Systems

Type 3275 is a direct-acting and general-purpose motor valve for shut-off, used as regulating unit in control loops. A stepper motor as actuator drives the valve which is incorporated in a compact and robust housing.

The integrated electronics simplify the process integration; additional actuation modules are not necessary. 

The drive shaft shifts a very smooth ceramic disc over a second fixed ceramic disc. The fixed ceramic disc is simultaneously the valve seat. By turning the ceramic disc the valve opens. The seat tightness is achieved by the very smooth surface of the stacked ceramic discs.

In case of power failure the actual valve position will be kept. Therefore, this valve is not suitable as safety shut-off valve. If a specific safety position in case of power failure is required, this can be realized by using an external buffer module.

The motor’s power consumption in opened or closed position is nearly zero. This key feature can reduce the energy consumption of a plant dramatically and thus make it more efficient.

Features

  •  Actuator isolated from flow path
  • Low power consumption
  • Fast response times
  • Orifice sizes DN 8 to 25 mm

Specifications

Seat/Seal Material

  • Seat Sealing: Technical Ceramics
  • FKM or NBR

Housing Material

  • Fluid: Brass
  • Fluid: Stainless Steel
  • Valve: Polycarbonate (PC)
  • Valve: Polyphenylene Sulfide (PPS)

Port Connection

  • G 1", G 1/2", G 3/4"
  • 1" NPT, 1/2" NPT, 3/4" NPT

Media

  • Liquids
  • Neutral Gases

Medium Temperature

  • 0° to 70° C (32° to 158° F)

Ambient Temperature

  • -10° to 60° C (14° to 140° F)

Environmental Protection

  • IP50

Pressure Range

  • psi: 0 to 90 (kPa: 0 to 600, bar: 0 to 6)

Electrical Connection

  • M12 Connector, 8-Pin, Male

Flow Rate

  • 1.8 to 9.6 m³/hour (Kvs) - Water

Power Supply

  • 24 Vdc ± 10 %, Max.

Power Consumption

  • 1 W (Holding Position)
  • 12 W, Max.

Duty Cycle

  • Up to 100 %

Response Time

  • Closure Time: 4 seconds

Input Signal

  • Binary Signal
  • PNP
  • 0-5 V (Log 0, Valve Closed)
  • 10-30 V (Log 1, Valve Open)

Output Signal

  • Load Capacity: 10-30 V, PNP, Max 100 mA

Mounting Position

  • Preferably with Actuator Upright

Orifice Size

  • 0.31" to 0.98" (8 to 25 mm)

Nominal Pressure

  • psig: 87 (kPa: 600, bar: 6)
show more