Voltage Accuracy
- Range: 1000 V
- Maximum Resolution: 0.1 V
- Accuracy: ± (0.2 % + 0.01 %)
Current Accuracy
- i17xx-flex 1500 12”: 150 A to 1500 A
- i17xx-flex 3000 24”: 300 A to 3000 A
- i17xx-flex 6000 36”: 600 A to 6000 A
- i40 s-EL clamp: 4 A to 40 A
Frequency
- Range: 42.5 Hz to 69 Hz
- Maximum Resolution: 0.01 Hz
- Intrinsic Accuracy: ± (0.1 %)
Aux Input
- Range: ± 10 V dc
- Maximum Resolution: 0.1 mV
- Intrinsic Accuracy: ± (0.2 % + 0.02 %)
Resolution
- 16-bit synchronous sampling
Sampling Frequency
- 10.24 kHz at 50/60 Hz, synchronized to mains frequency
Interfaces
- USB-A
- WiFi
- Bluetooth
- USB-mini
Number of Inputs
- Voltage: 4 (3-Phases and neutral)
- Current: 3, mode selected automatically for attached sensor
- Auxiliary & Wireless: 2
Operating Temperature
- -10° C to +50° C
- 14° F to 122° F
Enclosure
- IP50 in accordance with EN 60529
Vibration
- MIL-T-28800E, Type 3, Class III, Style B
Safety
- IEC 61010-1
- IEC 61010-2-031: CAT IV 600 V/CAT III 1000 V
Electromagnetic Compatibility
- EN 61326-1: Industrial CISPR 11: Group 1, Class A
- Korea (KCC): Class A Equipment
- USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103