Fluke 1760 Three-Phase Power Quality Recorder

Brand: Fluke Corporation

The Fluke 1760 Three-Phase Power Quality Recorder is fully compliant to IEC 61000-4-30 Class-A, for advanced power quality analysis and consistent compliance testing. 

Designed for analysis of utility and industrial power distribution systems, in medium- and low-voltage networks. 

The Fluke 1760 provides exceptional flexibility with the ability to customize thresholds, algorithms, and measurement selections. 

The 1760 power recorder captures the most comprehensive details on user-selected parameters; the supplied PQAnalyze application software enables users uses the in depth measurement and produce sophisticated analysis and reports.
Features
  • Fully Class-A compliant: Conduct tests according to the stringent international IEC 61000-4-30 Class-A standard
  • GPS time synchronization: Correlate data with events or datasets from other instruments with precision
  • Flexible and fully configurable thresholds and scale factors: Allows user to pinpoint specific issues by defining the detailed criteria for detection and recording of disturbances.
  • Uninterrupted power supply (40 minutes): Never miss important events - even record the beginning and end of interruptions and outages to help determine the cause
  • 2 GB data memory: Enables detailed, simultaneous recording of numerous power parameters for long periods of time
  • Comprehensive software included: Provides trend diagrams for root cause analysis, statistical summaries, report writing and real-time data monitoring in the online mode
  • Plug and play: Allows quick setup with automatic sensor detection; sensors are instrument powered, eliminating the need for batteries
  • Rugged field design: Insulated housing and a solid state design with no rotating components enable reliable testing under nearly any conditions

Specifications

Quality System

  • Developed and manufactured as per ISO 9001: 2000

Intrinsic Uncertainty

  • All specified intrinsic uncertainties are valid under these reference conditions

Data Memory

  • 2 GB flash memory

Interfaces

  • Ethernet (100 MB/s)
  • RS-232
  • external modem via RS-232

Working Temperature Range

  • -20° C to 50° C
  • -4° F to 122° F

Channel LEDs

  • 3-color LEDs per channel for: • overload condition • under load condition signal level in nominal range

Climatic Class

  • B2 (IEC 654-1), -20° C to 50° C (-4° F to +122° F)

Housing

  • Insulated, robust plastics housing

EMC

  • Emission: Class-A as per IEC/EN 61326-1
  • Immunity: IEC/EN 61326-1

Power Supply Range

  • AC: 83 V to 264 V, 45 to 65 Hz

Power Consumption

  • Maximum 54 VA

Signal Conditioning Range

  • 50 Hz ± 15 % (42.5 Hz to 57.5 Hz)
  • 60 Hz ± 15 % (51 Hz to 69 Hz)

Resolution

  • 16 ppm

Harmonics

  • as per IEC 61000-4-7:2002: 200 ms

Flicker

  • As per EN 61000-4-15:2003: 10 min (Pst), 2 h (Plt)

Number of Inputs

  • 8 galvanically isolated inputs for voltage and current measurements

Sensor Category Rating

  • Up to 600 V CAT IV depending on sensor

Nominal Voltage

  • 100 mV

Measurement Input Range

  • 280 mV

Overload Capacity

  • 1000 V, continuously

Input Resistance

  • 1 MΩ

Input Capacitance

  • 5 pF
show more